3.8/6.6kV Single Core Copper MV Power Cable

3.8/6.6kV Single Core Copper MV Power Cable
รายละเอียด:

• Conductor resistance AS/NZS 1125
• Insulation resistance AS/NZS 1429.1
• Voltage test AS/NZS 1429.1

• AS/NZS 1429.1
• AS/NZS 1125
• AS/NZS 3808
ส่งคำถาม
ดาวน์โหลด
คำอธิบาย
พารามิเตอร์ทางเทคนิค
การรับรอง
Copper Medium Voltage Cable

 

3.8/6.6kV Single Core Copper MV Power Cable

3.8/6.6kV single core copper MV power cable is made of stranded compacted circular copper, which has excellent conductivity, making it the preferred material for high-performance electrical cables. The stranded and compacted structure increases flexibility and reduces the overall diameter of the conductor, improving current-carrying capacity while maintaining mechanical strength. The compacted design also ensures better contact between strands, reducing energy loss and improving overall efficiency during power transmission.

Min. installation temperature: 0 degree

Operating temperature: -25 degree to +90 degree

Emergency operating temperature: 105 degree

Max. Short Circuit Temperature: 250 degree

 

 

 

Copper 3.8/6.6kV MV power cable are suitable for large infrastructure power distribution, such as factory power distribution, underground system power distribution, and transmit power from substations to various users. MV power cable are moisture-proof and corrosion-resistant, which can ensure long-term stable operation and avoid failures caused by the external environment.

Min. installation temperature: 0 degree

Operating temperature: -25 degree to +90 degree

Emergency operating temperature: 105 degree

(max. operation of 36hrs, at 3 periods for 12 consecutive months use)

Max. Short Circuit Temperature: 250 degree

STA cable application

 

 

Single Core Medium Voltage Cable

 

• Nominal Voltage: 3.8/6.6 (7.2) kV

• Conductor: Stranded Compacted Circular Copper conductor as per AS/NZS 1125

• Conductor Screen: Extruded Semi-conductive compound

• Insulation Screen: Extruded Strippable Semi-conductive compound

• Metallic Insulation Screen: Copper Wire Screen + helically applied copper tape (E/F current capacity – Based on requirement)

• Termite Protection: Polyamide (Nylon -12) (optional)

(Alternative Sheath: PVC+HDPE Composite Sheath or PVC + Nylon + HDPE

(composite sheath with anti-termite properties) or LSZH Outer sheath and parameters will change accordingly)

 

 

 

AS/NZS1429.1 MV power cable has been extensively tested to prove its reliability under different conditions, such as temperature fluctuations, humid environments, etc., to ensure the long-term stable operation of the cable in harsh environments, reduce safety risks such as electrical failures and fire, and protect the safety of users and equipment.

STA cable certification

 

 

sta power cable package

 

 

SAA cable factory

 

Greater Wire manufacturer uses fully automated production. The accuracy of automated production equipment can reach 0.002mm, and all products are 100% inspected and digitally marked. The company has a super large warehouse, with a daily production of 300000 meters, scalability, and timely delivery to protect your business. we have professional sales team. Our photovoltaic cables are supplied to many countries and regions around the world, such as Lebanon, Iraq, Myanmar, the Philippines, Germany, the United States, Sweden, South Africa, and other main countries and regions.

 

 

Company cases

 

 

greater wire Partner

 

 

Q:What are the main application scenarios of medium-voltage cables?

A: Medium-voltage cables are widely used in industries, power infrastructure, urban distribution networks, wind farms, photovoltaic power stations and other scenarios that require reliable power transmission.

Q: What is the difference between medium-voltage cables and high-voltage cables?

A: The voltage level of MV cables is lower than that of high-voltage cables. High-voltage cables are used for power transmission above 35kV, while medium-voltage cables are used for power distribution systems with lower voltages.

Q:What is the difference between aluminum-core medium-voltage cables and copper-core medium-voltage cables?

A:Aluminum-core cables are lighter and less expensive, but their conductivity is slightly inferior to that of copper-core cables. Copper-core cables have high conductivity and are suitable for applications with high current density requirements.

 

 

ป้ายกำกับยอดนิยม: 3.8/6.6kv single core copper mv power cable, China 3.8/6.6kv single core copper mv power cable manufacturers, suppliers, factory

MV105 cable

MV105 cable specification

 

mm2
1 16 12.9 14.8 19.0
1 25 14.1 16.0 20.0
1 35 15.1 17.0 21.0
1 50 16.2 18.1 22.0
1 70 17.9 19.8 24.0
1 95 19.4 21.3 25.0
1 120 21 22.9 27.0
1 150 22.4 24.3 28.0
1 185 24.1 26.0 30.0
1 240 26.6 28.5 33.0
1 300 29 30.9 35.0
1 400 32.2 34.1 39.0
1 500 36 37.9 43.0
1 630 39.6 41.5 47.0
1 800 43.3 45.2 50.0
1 1000 47.6 49.5 55.0
• Above mentioned parameters are based on 3k A/sec earth fault current capacity of copper screen
 
Max. DC Resistance at 20˚C
Max. AC Resistance at 90˚C

In ground at  20 degree
20 degree
In air at 30 degree

mm2
1 16 1.15 1.466 0.22 0.475 0.149 113 109 104 103 128 125
1 25 0.727 0.927 0.25 0.442 0.139 144 140 133 132 167 163
1 35 0.524 0.668 0.28 0.421 0.132 172 166 159 157 203 198
1 50 0.387 0.494 0.31 0.401 0.126 203 196 188 186 243 238
1 70 0.268 0.342 0.36 0.369 0.116 246 239 229 227 303 296
1 95 0.193 0.247 0.4 0.353 0.111 293 285 274 271 369 361
1 120 0.153 0.196 0.45 0.336 0.106 332 323 311 308 426 417
1 150 0.124 0.159 0.49 0.326 0.102 366 361 347 343 481 473
1 185 0.0991 0.128 0.54 0.316 0.099 410 406 391 387 550 543
1 240 0.0754 0.098 0.58 0.305 0.096 470 469 453 447 647 641
1 300 0.0601 0.079 0.59 0.299 0.094 524 526 510 504 739 735
1 400 0.047 0.063 0.62 0.291 0.091 572 590 571 564 837 845
1 500 0.0366 0.051 0.66 0.284 0.089 660 655 640 635 970 960
1 630 0.0283 0.042 0.74 0.276 0.087 735 730 715 710 1110 1100
1 800 0.0221 0.035 0.82 0.269 0.084 770 820 800 790 1260 1250
1 1000 0.0176 0.031 0.91 0.262 0.082 825 885 865 855 1420 1410
*: Current Ratings are based on IEC {{0}} & IEC 60287, Max. Conductor Temperature at 90 degree , Ambient temperature at 30 degree in Air / at 20 degree in Ground, Thermal resistivity of Soil 1.5 k.m/W & for earthenware ducts 1.2k.m/W and Depth of Laying 0.8m.
Current rating de-rating factors for other than 30 degree ambient air temperature.
20 25 35 40 45 50 55 60
1.08 1.04 0.96 0.91 0.87 0.82 0.76 0.71

 

Current rating de-rating factors for other than 20 degree ground temperature.
10 15 25 30 35 40 45 50
1.07 1.04 0.96 0.93 0.89 0.85 0.80 0.76

 

1 16 1.12 0.26 2.63 2.1 2.3
1 25 1.75 0.3 2.09 2.0 3.6
1 35 2.45 0.33 1.83 2.0 5.0
1 50 3.5 0.37 1.65 1.9 7.2
1 70 4.9 0.43 1.50 1.9 10.0
1 95 6.65 0.48 1.41 1.8 13.6
1 120 8.4 0.54 1.36 1.8 17.1
1 150 10.5 0.58 1.32 1.8 21.4
1 185 12.95 0.64 1.29 1.7 26.4
1 240 16.8 0.69 1.26 1.7 34.3
1 300 21 0.7 1.24 1.5 42.8
1 400 28 0.74 1.22 1.4 56.9
1 500 35 0.79 1.21 1.3 71.5
1 630 44.1 0.88 1.20 1.3 90.2
1 800 56 0.98 1.19 1.3 114
1 1000 70 1.09 1.19 1.3 143

 